Hioki-PW3360-20 Clamp On Power Logger

Code: PW3360-20

Clamp On Power Logger improvement of energy consumption in buildings or factories. Measuring range 600 V AC, Input Voltage 3 channels / Current 3 channels

Description

Hioki-PW3360-20 Clamp On Power Logger

The Hioki PW3360-20 Clamp On Power Meter is a multi-channel power measuring device utilizing clamp sensor input to accurately and safely measure power on single-phase to three-phase lines. The PW336020 compact 3-Phase 4-Wire energy logger monitors power demand and other power parameters to aid in energy audits and validate energy saving measures.

  • Voltage 3 channels / Current 3 channels
  • Single-phase 2-wire (1P2W, 1P2W 5 2 circuits, 1P2W 5 3 circuits)
  • Single-phase 3-wire (1P3W, 1P3W+I, 1P3W1U, 1P3W1U+I)Three-phase 3-wire (3P3W2M, 3P3W2M+I, 3P3W3M)
  • Three-phase 4-wire (3P4W), Current only: 1 to 3 channel

Voltage range

  • Measuring range 600 V AC
  • Total display area: 5V to 1000 V (less than 5 V displays as 0 V)
  • Effective measurement range: 90 V to 780 V, peak: ±1400V
  • Accuracy ±0.3% rdg. ±0.1% f.s.

Current range

  • – Load current
  • CLAMP ON SENSOR 9694 : 500m/1/5/10/50 A
  • CLAMP ON SENSOR 9695-02 : 500m/1/5/10/50 A
  • CLAMP ON SENSOR 9660 : 5/10/50/100 A
  • CLAMP ON SENSOR 9695-03 : 5/10/50/100 A
  • CLAMP ON SENSOR 9661 : 5/10/50/100/500 A
  • CLAMP ON SENSOR 9669 : 100/200/1k A
  • FLEXIBLE CLAMP ON SENSOR CT9667 : [50/100]*2 /500/[1kA]*2 /5k A
  • – Leakage current
  • LEAK CLAMP ON SENSOR 9657-10 : 50m/100m/500m/1/5 A
  • LEAK CLAMP ON SENSOR 9675 : 50m/100m/500m/1/5 A
  • Total display range: Within 0.4 to 130% of the range
  • Effective measurement range: Within 5 to 110% of the range peak: ±400% of range, however, maximum range is 200%.
  • Accuracy ±0.3% rdg. ±0.1% f.s. + clamp sensor accuracy

Power range

  • Measuring range 300.00 W to 9.0000 MW
  • Depends on voltage/current combination and measured line type (see Measurement Range Configuration Tables)
  • Total display range: Within 0 to 130% of the range (“0W” display indicates zero rms voltage and/or current)
  • Effective measurement area: Within 5 to 110% of the range
  • Accuracy ±0.3% rdg. ±0.1% f.s. +clamp sensor accuracy
  • Screen : 3.5″ TFT color LCD (320 × 240 pixel)
  • SD Card
  • Sampling interval Recording Frequency  1/2/5/10/15/30 s, 1/2/5/10/15/20/30/60 min
  • Use a LAN cable to connect the Unit to PC for real-time remote monitoring
  • USB Interface
  • Power supply AC Adapter
  • Size 180 x 100 x 48mm (550g)

Standard equipment

  • ตัวเครื่อง
  • Voltage Cord L9438-53 x 1 set
  • AC Adapter Z1006 x 1
  • USB cable x 1
  • Instruction manual x 1
  • Measurement guide x 1
  • Color spiral tubes x 1 set (Red, yellow, blue x 2 each)
  • For color-coding clamp sensors
  • Spiral tubes for grouping clamp sensor cords x 5

Accessory

PW9002
Battery Pack Set
Z4001
SD Memory Card 2GB
Clamp on Sensors
(Current Input)
Clamp on Leak
(Leak Current  Input)

Clamp on Sensor

9660
Clamp on Sensor (100A AC)
9661
Clamp on Sensor (500A AC)
9669
Clamp on Sensor (1000A AC)
9694
Clamp on Sensor (5A AC)
9695-02
Clamp on Sensor (50A)
9695-03
Clamp on Sensor (100A)
CT9667 AC Flexible Current Sensor (5000A/ 500 A AC) 9219 Connection cable for 9695-02/ 9695-03

Clamp on Leak

9657-10
Clamp on Leak (10A AC)
9675
Clamp on Leak (10A AC)

Video Hioki-PW3360-20

General Specifications
Display device 3.5 inch TFT color LCD (320 x 240 pixel)
Japanese, English (supported from version 1.50),
Chinese (Simplifi ed, supported from version 2.00)
Backlight auto-off function (after 2 minutes)
Operating environment Indoors, Pollution degree 2, altitude up to 2000 m (6562-ft.)
Operating temperature and humidity (no condensation) -10°C to 50°C (14°F to 122°F), 80% RH or less
During LAN communication: 0°C to 50°C (32°F to 122°F), 80% RH or less
During battery operation: 0°C to 40°C (32°F to 104°F), 80% RH or less
During battery charging: 10°C to 40°C (50°F to 104°F), 80% RH or less
Storage temperature and humidity (no condensation) -20°C to 60°C (-4°F to 140°F), 80% RH or less
However, the battery's storage temperature range is -20°C to
30°C (-4°F to 86°F), 80% RH or less
Dielectric strength 4.29 kVrms AC (1 mA sense current) between voltage input
terminals and external terminals, 50/ 60 Hz for 60 sec.
Applicable standards Safety: EN61010, EMC: EN61326, EN61000-3-2, EN61000-3-3
Power supply •Z1006 AC Adapter (12 V, 1.25 A), Rated supply voltage 100 VAC
to 240 VAC, Rated power supply frequency 50/60 Hz
•Model 9459 Battery Pack (Ni-MH DC7.2 V 2700 mAh)
Charge function Charges the battery regardless of whether the instrument is on or off.
Charge time: Max. 6 hr. 10 min. (reference value at 23°C)
Maximum rated power •When the Z1006 AC Adapter is used: 40 VA (including AC adapter),
13 VA (PW3360-20 instrument only)
•When the 9459 Battery Pack is used: 3 VA
Continuous battery operation time Approx. 8 hr. (Continuous, backlight off)
(when using the battery pack)
Backup battery life Clock and settings (Lithium battery), Approx. 10 years @23°C (@73.4°F)
Dimensions Approx. 180W(7.09") x 100H(3.94") x 48D (1.89") mm (without PW9002)
Approx. 180W(7.09") x 100H(3.94") x 68D (2.68") mm (with PW9002)
Mass Approx. 550g (19.4 oz) (without PW9002), Approx. 830g (29.3 oz) (with PW9002)
Accessories Voltage Cord L9438-53(1 set), AC Adapter Z1006 (1),
USB cable(1), instruction manual (1), measurement guide (1),
color spiral tubes (1 set): red, yellow, blue/two each, for color-coding clamp
sensors, spiral tubes for grouping clamp sensor cords (5)
Measurement Specifications
Connection Single-phase 2-wire (1P2W, 1P2W 5 2 circuits, 1P2W 5 3 circuits
Single-phase 3-wire (1P3W, 1P3W+I, 1P3W1U, 1P3W1U+I)
Three-phase 3-wire (3P3W2M, 3P3W2M+I, 3P3W3M)
Three-phase 4-wire (3P4W), Current only: 1 to 3 channels
Simultaneous power/current measurement modes 1P3W+I: 1 power circuit and 1 current channel
3P3W2M+I: 1 power circuit and 1 current channel
Measurement items Voltage RMS, current RMS, voltage fundamental wave value,
current fundamental wave value, voltage fundamental wave phase
angle, current fundamental wave phase angle, frequency (U1),
voltage waveform peak (absolute value), current waveform peak
(absolute value), active power, reactive power (with lag/lead
display), apparent power, power factor (with lag/lead display) or
displacement power factor (with lag/lead display), active energy
(consumption, regeneration), reactive energy (consumption
regeneration), electricity rate display (by means of planned future
function update), active power demand quantity (consumption
regeneration), reactive power demand quantity (lag, lead), active
power demand value (consumption, regeneration), reactive power
demand value (lag, lead), power factor demand, pulse input
Calculation selection Power factor, reactive and apparent power: rms calculation/
fundamental wave calculation
Measurement accuracy (50/ 60Hz, power factor = 1) Voltage: ±0.3% rdg. ±0.1% f.s.
Current: ±0.3% rdg. ±0.1% f.s. + clamp sensor accuracy
Active power: ±0.3% rdg. ±0.1% f.s. +clamp sensor accuracy
Clamp-On Sensor 9661 accuracy: ±0.3% rdg. ±0.01% f.s.
(Accuracy depends on clamp sensor. See page 6 for the accuracy of
each model, and page 7 for combined accuracy of Model PW3360-20
and each clamp sensor.)
Display update rate Approx. 0.5 sec (except when accessing SD card or internal memory,
or during LAN/USB communication)
Measurement method Digital sampling and zero cross synchronization calculation method
Sampling: 10.24 kHz (2048 points)
Calculation processing
50 Hz: Continuous, gapless measurement at 10 cycles
60 Hz: Continuous, gapless measurement at 12 cycles
A/D converter resolution 16bit