AC/DC |
Yes |
Fundamental frequency |
DC/ 50 Hz/ 60 Hz |
Measurement lines |
- Single-phase 2-wire
- single-phase 3-wire
- three-phase 3-wire
- three-phase 4-wire + Ch. 4
|
Voltage ranges |
1000.0 V rms or DC, Transient measurement 2.200 kV peak |
Current ranges |
- 50.000 mA AC to 5.0000 kA AC
- 10.000 A DC to 2.0000 kA DC
(depends on current sensor in use) |
Power ranges |
50.000 W to 6.0000 MW
(determined automatically based on current range in use) |
Basic accuracy |
Voltage: ±0.2% of nominal voltage
Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy
Active power: DC ±0.5 % rdg. ±0.5 % f.s. + current sensor accuracy
AC ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy |
Voltage input |
Number of channels |
4 (U4: Not isolated) |
Maximum terminal-toground rated voltage |
1000 V (measurement category III)
600 V (measurement category IV) |
Current input |
Number of channels |
4 |
Power supply for sensors |
Yes |
Measurement parameters |
Voltage |
- 1/2 RMS value (half-wave offset wave calculation)
- RMS value
- waveform peak
- Voltage DC
- Unbalance factor (negative-phase, zero-phase)
- frequency (1 wave/ 200 ms/ 10 sec.)
|
Crest factor |
Current |
- Inrush current (half-wave)
- RMS value
- waveform peak
- Current DC
- Unbalance factor (negative-phase, zero-phase)
- K factor
|
1/2 RMS value (half-wave offset wave calculation), crest factor |
Power |
- Active power
- Reactive power
- Apparent power
- Power factor,
- Displacement power factor
- Active energy
- Reactive energy
|
Apparent energy, Electrical charges |
Flicker |
Pst, Plt, ΔV10 (3 channels simultaneously) |
Harmonics |
- 0th order (DC) to 50th order
- Voltage/ Current/ Power
- Phase angle (voltage/ current)
- Voltage/Current phase difference
- Total harmonic distortion ratio (voltage/ current)
|
Inter-harmonics |
0.5 th order to 49.5 th order, voltage/ current |
High-order harmonics |
n/a |
Time-series measuremen |
Recording period |
Max. 1 year |
Recording interval time |
200 ms/600 ms/150 cycles (with 50 Hz input)/1/2/5/10/15/30 sec. to 2 h |
Event measurement |
Event statistical processing |
Displays the number of occurrences by event per day |
Waveform acquisition: |
Before event |
Max. 1 sec. |
At event |
200 ms |
After event |
Max. 10 sec. |
Event parameters |
Measurable event parameters |
Voltage Swell/ Dip/ Interruption/ Frequency fluctuations/ Inrush current/ THD |
Transient voltage |
200 kS/s, 2.2 kV |
Setting aid |
Quick Set |
Operating temperature and humidity |
-20 to 50°C / 80%RH |
IEC 61000-4-30 standard compliance |
Class S |
Protection Class |
IP54 (EN60529) with connection cable connected, but not including cable tip |
Power supply |
AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A),
Battery pack Z1003 (Continuous use: 8 hr Charging time: Max. 5 hr 30 m with AC adapter) |
Interfaces |
- SD/SDHC memory card
- RS-232C (for communication/ LR8410 link (Ver. up)
- LAN (HTTP server/ FTP (Ver. up)/ Send e-mail (Ver. up)
- USB 2.0 (for communication)
|
Dimension/ Weight |
300 x 211 x 68 mm / 2.5 kg |
Accessories |
Standard
- Instruction manual ×1
- Measurement guide ×1
- Voltage cord L1000-05 ×1 set
(Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5)
- Color clip (for identifying clamp sensor color) ×1 set
- Spiral tube ×5
- AC adapter Z1002 ×1
- Strap ×1
- USB cable (1 m 3.28 ft length) ×1
- Battery pack Z1003 ×1
- PQ ONE (software, CD)
Kit includes PQ3100-94
- AC FLEXIBLE CURRENT SENSOR (CT7045) x 4
- CARRYING CASE (C1009) x 1
- SD MEMORY CARD 2GB (Z4001) x 1
|